Which layers of the cooling chain do control offerings say they cover?各控制产品声称覆盖冷却链的哪些层级?
Most controls cover one or two cooling layers.多数控制产品只管冷却链的一到两个层级。
The missing link for AI sites, between fast-swinging IT load and the plant, is stated by only one offering and trialled by one more.AI 站点缺的是快速波动的 IT 负载与冷站之间的那一环:只有一家写明做到,另有一项试验以此为目标。
Evidence checked 2026-10-15证据核查 2026-10-15
| Offering产品 | IT liquid loop or CDUIT 侧液冷回路或 CDU | Leak detection漏液检测 | Room air units机房空调末端 | Chilled-water plant冷站 | Optimisation across units跨设备优化 | IT-side signals as an input以 IT 侧信号为输入 |
|---|---|---|---|---|---|---|
| Vertiv Liebert iCOM CWM chilled-water plant manager | not stated未披露 | not stated未披露 | stated已写明 | stated已写明 | not stated未披露 | not stated未披露 |
| Vertiv CoolChip CDU integrated controller | stated已写明 | stated已写明 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 |
| Schneider Electric (Motivair) Motivair CDU PLC control | stated已写明 | stated已写明 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 |
| Johnson Controls OpenBlue Central Utility Plant Optimization | not stated未披露 | not stated未披露 | not stated未披露 | stated已写明 | stated已写明 | not stated未披露 |
| Siemens White Space Cooling Optimization (WSCO) | not stated未披露 | not stated未披露 | stated已写明 | not stated未披露 | stated已写明 | not stated未披露 |
| Phaidra AI agents (liquid cooling, chiller staging) | stated已写明 | not stated未披露 | not stated未披露 | stated已写明 | stated已写明 | stated已写明 |
| Trane Tracer chiller plant control and AI Control for Water Systems | not stated未披露 | not stated未披露 | not stated未披露 | stated已写明 | stated已写明 | not stated未披露 |
| Carrier Coolant Distribution Unit controls (Europe) | stated已写明 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 |
| nVent RackChiller CDU controls | stated已写明 | stated已写明 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 |
| CoolIT Systems AHx180 CDU control and monitoring | stated已写明 | stated已写明 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 |
| Huawei iCooling@AI | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | stated已写明 | not stated未披露 |
| Stulz CyberAir 3PRO CW unit control | not stated未披露 | not stated未披露 | stated已写明 | not stated未披露 | not stated未披露 | not stated未披露 |
| Delta Liquid-to-liquid CDU 1,200 kW controls | stated已写明 | stated已写明 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 |
| Daikin with NTT DATA AI cooling control trial (not yet a product) | aim of a trial试验目标 | not stated未披露 | aim of a trial试验目标 | aim of a trial试验目标 | aim of a trial试验目标 | aim of a trial试验目标 |
- Vertiv Liebert iCOM CWM chilled-water plant manager
States: 写明:Room air units机房空调末端, 、Chilled-water plant冷站
Not stated: 未写明:IT liquid loop or CDUIT 侧液冷回路或 CDU, 、Leak detection漏液检测, 、Optimisation across units跨设备优化, 、IT-side signals as an input以 IT 侧信号为输入 - Vertiv CoolChip CDU integrated controller
States: 写明:IT liquid loop or CDUIT 侧液冷回路或 CDU, 、Leak detection漏液检测
Not stated: 未写明:Room air units机房空调末端, 、Chilled-water plant冷站, 、Optimisation across units跨设备优化, 、IT-side signals as an input以 IT 侧信号为输入 - Schneider Electric (Motivair) Motivair CDU PLC control
States: 写明:IT liquid loop or CDUIT 侧液冷回路或 CDU, 、Leak detection漏液检测
Not stated: 未写明:Room air units机房空调末端, 、Chilled-water plant冷站, 、Optimisation across units跨设备优化, 、IT-side signals as an input以 IT 侧信号为输入 - Johnson Controls OpenBlue Central Utility Plant Optimization
States: 写明:Chilled-water plant冷站, 、Optimisation across units跨设备优化
Not stated: 未写明:IT liquid loop or CDUIT 侧液冷回路或 CDU, 、Leak detection漏液检测, 、Room air units机房空调末端, 、IT-side signals as an input以 IT 侧信号为输入 - Siemens White Space Cooling Optimization (WSCO)
States: 写明:Room air units机房空调末端, 、Optimisation across units跨设备优化
Not stated: 未写明:IT liquid loop or CDUIT 侧液冷回路或 CDU, 、Leak detection漏液检测, 、Chilled-water plant冷站, 、IT-side signals as an input以 IT 侧信号为输入 - Phaidra AI agents (liquid cooling, chiller staging)
States: 写明:IT liquid loop or CDUIT 侧液冷回路或 CDU, 、Chilled-water plant冷站, 、Optimisation across units跨设备优化, 、IT-side signals as an input以 IT 侧信号为输入
Not stated: 未写明:Leak detection漏液检测, 、Room air units机房空调末端 - Trane Tracer chiller plant control and AI Control for Water Systems
States: 写明:Chilled-water plant冷站, 、Optimisation across units跨设备优化
Not stated: 未写明:IT liquid loop or CDUIT 侧液冷回路或 CDU, 、Leak detection漏液检测, 、Room air units机房空调末端, 、IT-side signals as an input以 IT 侧信号为输入 - Carrier Coolant Distribution Unit controls (Europe)
States: 写明:IT liquid loop or CDUIT 侧液冷回路或 CDU
Not stated: 未写明:Leak detection漏液检测, 、Room air units机房空调末端, 、Chilled-water plant冷站, 、Optimisation across units跨设备优化, 、IT-side signals as an input以 IT 侧信号为输入 - nVent RackChiller CDU controls
States: 写明:IT liquid loop or CDUIT 侧液冷回路或 CDU, 、Leak detection漏液检测
Not stated: 未写明:Room air units机房空调末端, 、Chilled-water plant冷站, 、Optimisation across units跨设备优化, 、IT-side signals as an input以 IT 侧信号为输入 - CoolIT Systems AHx180 CDU control and monitoring
States: 写明:IT liquid loop or CDUIT 侧液冷回路或 CDU, 、Leak detection漏液检测
Not stated: 未写明:Room air units机房空调末端, 、Chilled-water plant冷站, 、Optimisation across units跨设备优化, 、IT-side signals as an input以 IT 侧信号为输入 - Huawei iCooling@AI
States: 写明:Optimisation across units跨设备优化
Not stated: 未写明:IT liquid loop or CDUIT 侧液冷回路或 CDU, 、Leak detection漏液检测, 、Room air units机房空调末端, 、Chilled-water plant冷站, 、IT-side signals as an input以 IT 侧信号为输入 - Stulz CyberAir 3PRO CW unit control
States: 写明:Room air units机房空调末端
Not stated: 未写明:IT liquid loop or CDUIT 侧液冷回路或 CDU, 、Leak detection漏液检测, 、Chilled-water plant冷站, 、Optimisation across units跨设备优化, 、IT-side signals as an input以 IT 侧信号为输入 - Delta Liquid-to-liquid CDU 1,200 kW controls
States: 写明:IT liquid loop or CDUIT 侧液冷回路或 CDU, 、Leak detection漏液检测
Not stated: 未写明:Room air units机房空调末端, 、Chilled-water plant冷站, 、Optimisation across units跨设备优化, 、IT-side signals as an input以 IT 侧信号为输入 - Daikin with NTT DATA AI cooling control trial (not yet a product)
Aims of a trial: 试验目标:IT liquid loop or CDUIT 侧液冷回路或 CDU, 、Room air units机房空调末端, 、Chilled-water plant冷站, 、Optimisation across units跨设备优化, 、IT-side signals as an input以 IT 侧信号为输入
Not stated: 未写明:Leak detection漏液检测
● = the vendor's own page, datasheet or release says so (hover or focus for the wording). △ = stated only as the aim of a trial, not counted. ○ = not found in the cited sources; it may still exist. This is coverage as stated, not performance or quality. Columns: IT liquid loop = the loop serving IT equipment (CDU, secondary loop); chiller water flow counts under Plant and a valve on a room unit under Room air; Optimisation = across several units and described as AI, machine learning or model-based; IT-side signals = server, GPU or rack power, telemetry or workload used as a control input.● = 厂商自己的网页、数据表或公告写明(悬停或聚焦可看原文)。△ = 仅作为试验目标写明,不计入统计。○ = 在所引来源中未找到,不代表一定没有。这里只反映厂商写明的覆盖范围,不代表性能或质量。各列:IT 侧液冷回路 = 为 IT 设备供液的回路(CDU、二次侧);冷机水流量归入冷站,机房空调末端的水阀归入机房空调末端;跨设备优化 = 跨多台设备、且写明为 AI、机器学习或模型方法;IT 侧信号 = 以服务器、GPU 或机柜功率、遥测或负载作为控制输入。
| Offering产品 | Layer层级 | Vendor wording厂商原文 | Source来源 |
|---|---|---|---|
| Vertiv Liebert iCOM CWM chilled-water plant manager | Room air units机房空调末端 | “Liebert® iCOM CWM can control up to 16 Chillers and 32 indoor chilled water units belonging to the same system” | link链接 |
| Vertiv Liebert iCOM CWM chilled-water plant manager | Chilled-water plant冷站 | “Chiller Teamwork optimization both in constant and variable flow” | link链接 |
| Vertiv CoolChip CDU integrated controller | IT liquid loop or CDUIT 侧液冷回路或 CDU | “The integrated Vertiv™ CoolChip CDU controller allows temperature and flow to adapt to workload demands” | link链接 |
| Vertiv CoolChip CDU integrated controller | Leak detection漏液检测 | “Closed-loop pipe design with integrated leak detection” | link链接 |
| Schneider Electric (Motivair) Motivair CDU PLC control | IT liquid loop or CDUIT 侧液冷回路或 CDU | “Each CDU precisely controls required coolant flow based on IT cooling system needs.” | link链接 |
| Schneider Electric (Motivair) Motivair CDU PLC control | Leak detection漏液检测 | “Leak Detection (WDS Single|Redundant): Std.|Optional” | link链接 |
| Johnson Controls OpenBlue Central Utility Plant Optimization | Chilled-water plant冷站 | “CUPO continuously identifies the most efficient combination of chillers, towers, pumps and heat exchangers.” | link链接 |
| Johnson Controls OpenBlue Central Utility Plant Optimization | Optimisation across units跨设备优化 | “By combining real-time data, predictive algorithms and AI-driven supervisory control software” | link链接 |
| Siemens White Space Cooling Optimization (WSCO) | Room air units机房空调末端 | “A dense sensor network and an AI engine continuously model white space airflow and autonomously adjust cooling units” | link链接 |
| Siemens White Space Cooling Optimization (WSCO) | Optimisation across units跨设备优化 | “uses AI algorithms to optimize the operation strategy of the refrigeration system in real time and dynamically adjust the cooling parameters” | link链接 |
| Phaidra AI agents (liquid cooling, chiller staging) | IT liquid loop or CDUIT 侧液冷回路或 CDU | “The Agent proactively adjusts CDU setpoints in seconds to maintain thermal stability under volatile AI workloads.” | link链接 |
| Phaidra AI agents (liquid cooling, chiller staging) | Chilled-water plant冷站 | “The AI agent that proactively stages chillers to safely absorb facility-level power spikes while minimizing PUE.” | link链接 |
| Phaidra AI agents (liquid cooling, chiller staging) | Optimisation across units跨设备优化 | “A continuous learning model that orchestrates decisions across your complex systems.” | link链接 |
| Phaidra AI agents (liquid cooling, chiller staging) | IT-side signals as an input以 IT 侧信号为输入 | “Phaidra uses real time rack power as a leading indicator to detect workload spikes before temperatures rise.” | link链接 |
| Trane Tracer chiller plant control and AI Control for Water Systems | Chilled-water plant冷站 | “Tracer chiller plant control runs sophisticated strategies that dynamically manage the rotation, staging and sequencing of multiple chillers” | link链接 |
| Trane Tracer chiller plant control and AI Control for Water Systems | Optimisation across units跨设备优化 | “The functionality continuously learns and helps adjust chiller plant setpoints to help improve plant efficiency” | link链接 |
| Carrier Coolant Distribution Unit controls (Europe) | IT liquid loop or CDUIT 侧液冷回路或 CDU | “Its advanced controls allow precise management of secondary coolant loops” | link链接 |
| nVent RackChiller CDU controls | IT liquid loop or CDUIT 侧液冷回路或 CDU | “By managing the critical exchange between facility water and the secondary equipment loop, nVent CDUs ensure precise temperature and flow control for mission-critical IT loads.” | link链接 |
| nVent RackChiller CDU controls | Leak detection漏液检测 | “Leak Detection: Integrated sensors provide immediate alerts to prevent damage to IT equipment.” | link链接 |
| CoolIT Systems AHx180 CDU control and monitoring | IT liquid loop or CDUIT 侧液冷回路或 CDU | “sharing sensor telemetry and coordinating pump, flow, and alert states across the cluster” | link链接 |
| CoolIT Systems AHx180 CDU control and monitoring | Leak detection漏液检测 | “Integrated sensors: flow, pressure, temperature, humidity, coolant level and leak detection.” | link链接 |
| Huawei iCooling@AI | Optimisation across units跨设备优化 | “Through in-depth machine learning, this solution analyzes a large amount of historical data, identifies key factors that affect energy consumption, and obtains a PUE forecast model.” | link链接 |
| Stulz CyberAir 3PRO CW unit control | Room air units机房空调末端 | “Control based on the supply air, return air, room air or server inlet temperature” | link链接 |
| Delta Liquid-to-liquid CDU 1,200 kW controls | IT liquid loop or CDUIT 侧液冷回路或 CDU | “providing effective separation of facility and secondary circuits as well as precise control over flow, pressure, temperature, and coolant quality” | link链接 |
| Delta Liquid-to-liquid CDU 1,200 kW controls | Leak detection漏液检测 | “Leak detection: instant alarms with configurable response for efficient pumping action” | link链接 |
| Daikin with NTT DATA AI cooling control trial (not yet a product) | IT liquid loop or CDUIT 侧液冷回路或 CDU (aim of a trial)(试验目标) | “データセンター運用データと空調制御AIを活用し、空調・熱源・液体冷却設備の統合制御をめざす” | link链接 |
| Daikin with NTT DATA AI cooling control trial (not yet a product) | Room air units机房空调末端 (aim of a trial)(试验目标) | “データセンター運用データと空調制御AIを活用し、空調・熱源・液体冷却設備の統合制御をめざす” | link链接 |
| Daikin with NTT DATA AI cooling control trial (not yet a product) | Chilled-water plant冷站 (aim of a trial)(试验目标) | “データセンター運用データと空調制御AIを活用し、空調・熱源・液体冷却設備の統合制御をめざす” | link链接 |
| Daikin with NTT DATA AI cooling control trial (not yet a product) | Optimisation across units跨设备优化 (aim of a trial)(试验目标) | “予測結果に基づき、空調・熱源・液体冷却設備などを統合制御することで、安定したシステム運用とエネルギー利用の最適化を実現します。” | link链接 |
| Daikin with NTT DATA AI cooling control trial (not yet a product) | IT-side signals as an input以 IT 侧信号为输入 (aim of a trial)(试验目标) | “サーバーの電力使用状況や温度情報などの間接データをもとに、AIがサーバー内部の熱状態を予測することが特長です。” | link链接 |
- Vertiv Liebert iCOM CWM chilled-water plant managerVertiv Liebert iCOM CWM chilled-water plant manager
- Vertiv CoolChip CDU integrated controllerVertiv CoolChip CDU integrated controller
- Schneider Electric (Motivair) Motivair CDU PLC controlSchneider Electric (Motivair) Motivair CDU PLC control
- Johnson Controls OpenBlue Central Utility Plant OptimizationJohnson Controls OpenBlue Central Utility Plant Optimization
- Siemens White Space Cooling Optimization (WSCO)Siemens White Space Cooling Optimization (WSCO)
- Phaidra AI agents (liquid cooling, chiller staging)Phaidra AI agents (liquid cooling, chiller staging)
- Trane Tracer chiller plant control and AI Control for Water SystemsTrane Tracer chiller plant control and AI Control for Water Systems
- Carrier Coolant Distribution Unit controls (Europe)Carrier Coolant Distribution Unit controls (Europe)
- nVent RackChiller CDU controlsnVent RackChiller CDU controls
- CoolIT Systems AHx180 CDU control and monitoringCoolIT Systems AHx180 CDU control and monitoring
- Huawei iCooling@AIHuawei iCooling@AI
- Stulz CyberAir 3PRO CW unit controlStulz CyberAir 3PRO CW unit control
- Delta Liquid-to-liquid CDU 1,200 kW controlsDelta Liquid-to-liquid CDU 1,200 kW controls
- Daikin with NTT DATA AI cooling control trial (not yet a product)Daikin with NTT DATA AI cooling control trial (not yet a product)
14 offerings from thermal makers, building-control firms and software specialists. The six layers follow the heat path on the system map.14 个产品,来自热管理厂商、楼宇控制公司和软件公司。六个层级按系统图上的热路径划分。
Offerings that state they use IT-side signals (server, GPU or rack power, workload) as a control input写明以 IT 侧信号(服务器、GPU 或机柜功率、负载)为控制输入的产品
Offerings that state they control a liquid loop or CDU写明控制液冷回路或 CDU 的产品
Offerings that state an improvement figure for themselves; they measure different things (energy, PUE, cooling cost) and none gives a baseline and test conditions that allow a comparison给出自身改善幅度数字的产品;它们衡量的东西不同(能耗、PUE、冷却成本),也没有一个给出可供比较的基准和测试条件
The owner's judgement作者判断
Cooling controls decide how fast pumps run, which chillers start and where the air goes. Which layers of the cooling chain do the main control offerings say they cover?冷却控制决定水泵转多快、开哪台冷机、空气往哪里走。主要控制产品声称覆盖冷却链的哪些层级?
Willow Lei · judgementWillow Lei · 判断
Of the 14 control offerings read here, most equipment controllers cover their own unit; only Phaidra states control of both the CDU and the chiller plant, and only Phaidra states that it uses rack power as an input.
In my judgement the missing link for AI sites is between the IT load and the plant, because GPU power can swing within seconds.
Improvement claims cannot be compared yet, because none of the four that give a figure publishes a baseline and test conditions; until a common test exists, I read this table as coverage the vendors state, not as performance.
这里读到的 14 个控制产品中,大多数设备控制器只管本机;只有 Phaidra 写明同时控制 CDU 和冷站,也只有 Phaidra 写明以机柜功率为输入。
我的判断是:AI 站点缺的是 IT 负载与冷站之间的那一环,因为 GPU 功率可在数秒内波动。
改善幅度的说法目前无法比较,给出数字的 4 个产品都没有公布基准和测试条件;在出现共同的测试之前,我把这张表读作厂商写明的覆盖范围,而不是性能。
Timeline slice: the latest six events that happened, then the stated plans时间轴切片:最近六个已发生事件,然后是公布的计划
- Ecolab agrees to acquire CoolIT Systems, a maker of CDUs and cold platesEcolab 同意收购 CDU 和冷板制造商 CoolIT Systems Acquisitions, partnerships and funding收购、合作与融资 source来源
- Vertiv makes the CoolChip CDU 2300, with its integrated controller, available in EMEAVertiv 在欧洲、中东和非洲推出带集成控制器的 CoolChip CDU 2300 Control launches控制产品发布 source来源
- Daikin and NTT DATA announce a joint trial of AI that predicts server heat and controls air, plant and liquid-cooling equipment together大金与 NTT DATA 宣布联合试验:用 AI 预测服务器内部热状态,并统一控制空调、冷热源和液冷设备 Control launches控制产品发布 source来源
- Ecolab completes the CoolIT acquisition (about USD 4.75 billion)艺康完成收购 CoolIT(约 47.5 亿美元) Acquisitions, partnerships and funding收购、合作与融资 source来源
- Trane introduces AI Control for Water Systems, Chiller Plant Manager and Data Hall Team ControlTrane 推出水系统 AI 控制、冷站管理器和数据机房群控 Control launches控制产品发布 source来源
- Aligned Data Centers and Phaidra agree to deploy Phaidra Prism, a read-only AI operations layer, across Aligned's data centresAligned Data Centers 与 Phaidra 合作,在其数据中心部署只读的 AI 运维层 Phaidra Prism Acquisitions, partnerships and funding收购、合作与融资 source来源
- Planned计划 Daikin and NTT DATA aim to commercialise their AI cooling-control solution within fiscal 2027大金与 NTT DATA 计划在 2027 财年内将 AI 冷却控制方案商用 announced 2026-06-292026-06-29 公布 Control launches控制产品发布 source来源
Filled dot: happened. Hollow dot and "Planned": a stated plan with its window; it stays a plan until a source confirms it happened. The full six-year roadmap is further down.实心点:已发生。空心点加"计划":公司公布的计划及其时间窗口;在有来源确认发生前一直是计划。完整六年路线图在下方。
Full roadmap 2023 Q4 – 2029 Q3 (19 events), who earns the revenue, and the method完整路线图 2023 年第四季度至 2029 年第三季度(19 个事件)、谁获得收入、方法
Roadmap, 2023 Q4 – 2029 Q3路线图,2023 年第四季度至 2029 年第三季度
Dated events from official sources. Planned events show the window the source states; passing the window does not prove shipment. No future model is inferred.来自官方来源的有日期事件。计划事件显示来源给出的时间窗口;窗口过去并不代表已经出货。不推测未来型号。
Control launches控制产品发布
- Feb 20252025 年 2 月 Carrier launches QuantumLeap, a data-centre thermal management suite that includes controlsCarrier 推出 QuantumLeap 数据中心热管理系列,其中包括控制系统
- Sep 20252025 年 9 月 Trane extends its Tracer chiller plant control programming for data centresTrane 将 Tracer 冷站控制程序扩展到数据中心
- Dec 20252025 年 12 月 Siemens launches Data Center Solution 5.0 in China, including White Space Cooling Optimization, for which it claims up to 40% cooling energy savingsSiemens 在中国推出数据中心解决方案 5.0,包括机房冷却优化(WSCO),厂商称冷却能耗最多节省 40%
- Jan 20262026 年 1 月 Carrier introduces a coolant distribution unit with advanced controls for European data centresCarrier 面向欧洲数据中心推出带高级控制的冷却液分配单元
- Mar 20262026 年 3 月 Phaidra publishes an AI method for liquid-cooling control, with a white paper by Phaidra, NVIDIA, CoreWeave and Applied DigitalPhaidra 发布液冷 AI 控制方法,并与 NVIDIA、CoreWeave 和 Applied Digital 联合发布白皮书
- May 20262026 年 5 月 Vertiv makes the CoolChip CDU 2300, with its integrated controller, available in EMEAVertiv 在欧洲、中东和非洲推出带集成控制器的 CoolChip CDU 2300
- Sep 20262026 年 9 月 Trane introduces AI Control for Water Systems, Chiller Plant Manager and Data Hall Team ControlTrane 推出水系统 AI 控制、冷站管理器和数据机房群控
- Jun 20262026 年 6 月 Daikin and NTT DATA announce a joint trial of AI that predicts server heat and controls air, plant and liquid-cooling equipment together大金与 NTT DATA 宣布联合试验:用 AI 预测服务器内部热状态,并统一控制空调、冷热源和液冷设备
- Target Fiscal 2027 (April 2027 – March 2028)目标 2027 财年(2027 年 4 月至 2028 年 3 月) Daikin and NTT DATA aim to commercialise their AI cooling-control solution within fiscal 2027大金与 NTT DATA 计划在 2027 财年内将 AI 冷却控制方案商用 announced Jun 20262026 年 6 月公布 planned计划
Acquisitions, partnerships and funding收购、合作与融资
- Dec 20242024 年 12 月 Trane Technologies agrees to acquire BrainBox AI, a maker of autonomous HVAC controls (completion confirmed by Trane)Trane Technologies 同意收购自主暖通控制公司 BrainBox AI(Trane 已确认完成)
- Feb 20252025 年 2 月 Schneider Electric completes 75% of Motivair施耐德完成收购 Motivair 75% 股权 preliminary初步
- Aug 20252025 年 8 月 Daikin Applied agrees to acquire DDC Solutions, whose cabinets include software for automated cooling adjustment per cabinetDaikin Applied 同意收购 DDC Solutions,其机柜带有按机柜自动调节冷却的软件
- Aug 20252025 年 8 月 Vertiv acquires Waylay NV, a Belgian automation and generative AI software company, for monitoring and controlVertiv 收购比利时自动化和生成式 AI 软件公司 Waylay NV,用于监控与控制
- Sep 20252025 年 9 月 Schneider Electric announces reference designs with NVIDIA, the first covering integrated power management and liquid-cooling controlSchneider Electric 与 NVIDIA 发布参考设计,第一份涵盖电力管理与液冷控制的集成
- Oct 20252025 年 10 月 Phaidra, a maker of AI control agents, raises a Series B of more than USD 50 millionAI 控制智能体公司 Phaidra 完成超过 5,000 万美元的 B 轮融资
- Dec 20252025 年 12 月 Siemens and nVent announce they are developing a joint liquid-cooling and power reference architecture for AI data centresSiemens 与 nVent 宣布联合开发面向 AI 数据中心的液冷与电力参考架构
- Mar 20262026 年 3 月 Ecolab agrees to acquire CoolIT Systems, a maker of CDUs and cold platesEcolab 同意收购 CDU 和冷板制造商 CoolIT Systems
- Jul 20262026 年 7 月 Ecolab completes the CoolIT acquisition (about USD 4.75 billion)艺康完成收购 CoolIT(约 47.5 亿美元)
- Sep 20262026 年 9 月 Aligned Data Centers and Phaidra agree to deploy Phaidra Prism, a read-only AI operations layer, across Aligned's data centresAligned Data Centers 与 Phaidra 合作,在其数据中心部署只读的 AI 运维层 Phaidra Prism
Who earns the revenue谁获得这部分收入
Listed companies in the registry behind the products on this page: 本页产品背后、在上市公司名单中的公司:VertivVertiv, Schneider ElectricSchneider Electric, Johnson ControlsJohnson Controls, Trane TechnologiesTrane Technologies, CarrierCarrier, nVentnVent, DaikinDaikin, Delta Electronics台达电子. Outside the registry: 不在名单中:Siemens (listed in Frankfurt, not yet in the registry法兰克福上市,尚未列入名单); CoolIT Systems (part of Ecolab (listed, not in the registry)属于 Ecolab(上市,不在名单中)); Huawei (not listed非上市); Stulz (private非上市); Phaidra (private非上市). See the value-chain map查看产业链地图
Method方法
Each ● rests on a verbatim quote from the vendor's own page, datasheet or press release, checked word for word against the source text by script (scripts/research/check_quotes.mjs). ○ means the cited sources do not say it. No performance is compared: vendors publish no common test for control systems. Events come from company announcements. Evidence cut-off 2026-10-15. Personal research, not investment advice.每个 ● 都基于厂商自己的网页、数据表或新闻稿的原文引用,并由脚本逐字对照来源原文核对(scripts/research/check_quotes.mjs)。○ 表示所引来源未写明。不比较性能:控制系统没有厂商共同采用的测试。事件来自公司公告。证据截止 2026-10-15。个人研究,不构成投资建议。
Database view: the full controls matrix数据库视图:完整控制矩阵14 rows14 行
Each stated cell gives the vendor's wording; improvement figures are vendor claims. ○ = not stated by the vendor (explained once here, not repeated in words in each cell).每个已写明的单元格给出厂商原文;改善幅度数字为厂商说法。○ = 厂商未标称(只在此说明一次,不在每格重复文字)。
| Company and line公司与产品 | Kind类型 | IT liquid loop or CDUIT 侧液冷回路或 CDU | Leak detection漏液检测 | Room air units机房空调末端 | Chilled-water plant冷站 | Optimisation across units跨设备优化 | IT-side signals as an input以 IT 侧信号为输入 | Stated improvement (energy, PUE or cost)厂商宣称的改善幅度(能耗、PUE 或成本) | Notes说明 |
|---|---|---|---|---|---|---|---|---|---|
| Carrier Coolant Distribution Unit controls (Europe) | Controller控制器 | “Its advanced controls allow precise management of secondary coolant loops” | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | The QuantumLeap suite (February 2025) mentions "real-time optimization" without naming a method, so the optimisation column is not marked.QuantumLeap 系列(2025 年 2 月)提到“实时优化”,但未写方法,所以优化列未标记。 |
| CoolIT Systems AHx180 CDU control and monitoring | Controller控制器 | “sharing sensor telemetry and coordinating pump, flow, and alert states across the cluster” | “Integrated sensors: flow, pressure, temperature, humidity, coolant level and leak detection.” | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | A liquid-to-air CDU; group control covers up to 20 CDUs on one secondary network. CoolIT is now part of Ecolab.液-气 CDU;群控最多覆盖同一二次侧网络上的 20 台 CDU。CoolIT 现属 Ecolab。 |
| Daikin with NTT DATA AI cooling control trial (not yet a product) | Service服务 | Aim of a trial: 试验目标:“データセンター運用データと空調制御AIを活用し、空調・熱源・液体冷却設備の統合制御をめざす” | not stated未披露 | Aim of a trial: 试验目标:“データセンター運用データと空調制御AIを活用し、空調・熱源・液体冷却設備の統合制御をめざす” | Aim of a trial: 试验目标:“データセンター運用データと空調制御AIを活用し、空調・熱源・液体冷却設備の統合制御をめざす” | Aim of a trial: 试验目标:“予測結果に基づき、空調・熱源・液体冷却設備などを統合制御することで、安定したシステム運用とエネルギー利用の最適化を実現します。” | Aim of a trial: 试验目标:“サーバーの電力使用状況や温度情報などの間接データをもとに、AIがサーバー内部の熱状態を予測することが特長です。” | not stated未披露 | Announced 2026-06-29 (Japanese release). The cells are aims of a trial at an NTT DATA data centre, July 2026 to March 2027; commercialisation is targeted within fiscal 2027.2026-06-29 公布(日文发布稿)。这些单元格是在 NTT DATA 数据中心试验(2026 年 7 月至 2027 年 3 月)的目标;计划在 2027 财年内商用。 |
| Delta Liquid-to-liquid CDU 1,200 kW controls | Controller控制器 | “providing effective separation of facility and secondary circuits as well as precise control over flow, pressure, temperature, and coolant quality” | “Leak detection: instant alarms with configurable response for efficient pumping action” | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | Leak detection is also listed as standard in the specifications.规格中也列出漏液检测为标配。 |
| Huawei iCooling@AI | Software软件 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | “Through in-depth machine learning, this solution analyzes a large amount of historical data, identifies key factors that affect energy consumption, and obtains a PUE forecast model.” source来源 | not stated未披露 | PUE improved by 8 to 15% (the same page also says energy use is cut by 8 to 15%), compared with manual configuration; no result is given for the named sitePUE 改善 8% 至 15%(同页也写能耗降低 8% 至 15%),对照为人工配置;未给出所提站点的结果 “improving data centers' PUE by 8 to 15 percent” source来源 | Launched in 2018. A deep neural network model compares predicted and actual efficiency and sends optimised parameters to the cooling control system, which the case page says makes cooling components "collaborate"; it does not name the units adjusted. The case mentions China Unicom's Central Plains Data Center but gives no site result.2018 年推出。用深度神经网络模型对比预测与实际能效,并把优化参数下发给冷却控制系统;案例页称这使冷却部件“协同”运行,但未写调节哪些设备。案例提到中国联通中原数据中心,但未给出该站点的结果。 |
| Johnson Controls OpenBlue Central Utility Plant Optimization | Software软件 | not stated未披露 | not stated未披露 | not stated未披露 | “CUPO continuously identifies the most efficient combination of chillers, towers, pumps and heat exchangers.” | “By combining real-time data, predictive algorithms and AI-driven supervisory control software” | not stated未披露 | 10.2% estimated reduction in energy use at a Las Vegas resort and casino plant (not a data centre): a manually operated building automation system was replaced with CUPO, Metasys and an operations contract, with Auto Mode on more than 90% of the year拉斯维加斯一家度假村和赌场的冷站(不是数据中心)估算能耗降低 10.2%:人工操作的楼宇自控系统被替换为 CUPO、Metasys 和运维合同,全年超过 90% 时间处于自动模式 “10.2% estimated annual energy use savings” source来源 | General central-plant software, not data-centre specific in the pages read.所读页面中为通用的中央冷站软件,并非专门面向数据中心。 |
| nVent RackChiller CDU controls | Controller控制器 | “By managing the critical exchange between facility water and the secondary equipment loop, nVent CDUs ensure precise temperature and flow control for mission-critical IT loads.” | “Leak Detection: Integrated sensors provide immediate alerts to prevent damage to IT equipment.” | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | Remote control over Ethernet, SNMP v3 and Modbus is listed on the CDU800 sheet.CDU800 资料列出通过以太网、SNMP v3 和 Modbus 的远程控制。 |
| Phaidra AI agents (liquid cooling, chiller staging) | Software软件 | “The Agent proactively adjusts CDU setpoints in seconds to maintain thermal stability under volatile AI workloads.” source来源 | not stated未披露 | not stated未披露 | “The AI agent that proactively stages chillers to safely absorb facility-level power spikes while minimizing PUE.” | “A continuous learning model that orchestrates decisions across your complex systems.” | “Phaidra uses real time rack power as a leading indicator to detect workload spikes before temperatures rise.” source来源 | 30% lower cooling cost (a cost, not energy), "measured in production environments"; baseline and sites not stated冷却成本降低 30%(成本,不是能耗),“在生产环境中测得”;未写基准和站点 “30 % reduction in cooling costs” source来源 | Phaidra Prism, deployed by Aligned from September 2026, is described as a read-only intelligence layer; the control agents are separate products. A March 2026 white paper with NVIDIA, CoreWeave and Applied Digital compares against tuned PID control.Aligned 自 2026 年 9 月部署的 Phaidra Prism 被描述为只读的智能层;控制智能体是另外的产品。2026 年 3 月与 NVIDIA、CoreWeave 和 Applied Digital 合作的白皮书以调好的 PID 控制为对照。 |
| Schneider Electric (Motivair) Motivair CDU PLC control | Controller控制器 | “Each CDU precisely controls required coolant flow based on IT cooling system needs.” | “Leak Detection (WDS Single|Redundant): Std.|Optional” | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | Leak detection is standard or optional by model. A 2025 reference design with NVIDIA describes interoperability with NVIDIA Mission Control; that is not stated as a control input, so the IT-signal column is not marked.漏液检测按型号为标配或选配。2025 年与 NVIDIA 的参考设计提到与 NVIDIA Mission Control 互通;这未写成控制输入,所以 IT 侧信号列未标记。 |
| Siemens White Space Cooling Optimization (WSCO) | Software软件 | not stated未披露 | not stated未披露 | “A dense sensor network and an AI engine continuously model white space airflow and autonomously adjust cooling units” | not stated未披露 | “uses AI algorithms to optimize the operation strategy of the refrigeration system in real time and dynamically adjust the cooling parameters” source来源 | not stated未披露 | Up to 40% lower cooling energy, payback under 3 years; no baseline or site stated冷却能耗最多节省 40%,投资回收期少于 3 年;未写基准或站点 “which can achieve up to 40% cooling energy consumption savings, and the return on investment cycle is less than 3 years” source来源 | Described for air-cooled white space; the pages read do not mention liquid cooling. The saving comes from the China Data Center Solution 5.0 release (2025-12-11).描述对象为风冷机房;所读页面未提液冷。节能数字来自中国数据中心解决方案 5.0 发布稿(2025-12-11)。 |
| Stulz CyberAir 3PRO CW unit control | Controller控制器 | not stated未披露 | not stated未披露 | “Control based on the supply air, return air, room air or server inlet temperature” | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | Server inlet temperature is an air temperature at the rack, not an IT-side power or workload signal. Standby management and pressure control are also listed.服务器进风温度是机柜处的空气温度,不是 IT 侧功率或负载信号。还列出了备用管理和压差控制。 |
| Trane Tracer chiller plant control and AI Control for Water Systems | Platform平台 | not stated未披露 | not stated未披露 | not stated未披露 | “Tracer chiller plant control runs sophisticated strategies that dynamically manage the rotation, staging and sequencing of multiple chillers” | “The functionality continuously learns and helps adjust chiller plant setpoints to help improve plant efficiency” source来源 | not stated未披露 | not stated未披露 | Data Hall Team Control (September 2026) joins several cooling units into one system, but the release does not name the unit type, so the room-air column is not marked. The "up to 25%" energy figure in the BrainBox AI acquisition release is a general claim for commercial buildings, not a result stated for this product, so it is not counted.Data Hall Team Control(2026 年 9 月)把多台冷却机组联成一个系统,但发布稿未写机组类型,所以机房空调末端列未标记。BrainBox AI 收购公告中“最多 25%”的能耗数字是对一般商业建筑的说法,并非该产品的标称结果,所以不计入。 |
| Vertiv CoolChip CDU integrated controller | Controller控制器 | “The integrated Vertiv™ CoolChip CDU controller allows temperature and flow to adapt to workload demands” source来源 | “Closed-loop pipe design with integrated leak detection” | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | "Adapt to workload demands" is not described as reading IT signals, so that column is not marked. Group control and load sharing across units are listed; no AI optimisation is stated.“适应工作负载需求”未说明读取 IT 侧信号,所以该列未标记。列出了多台机组的群控和负载分配;未写 AI 优化。 |
| Vertiv Liebert iCOM CWM chilled-water plant manager | Controller控制器 | not stated未披露 | not stated未披露 | “Liebert® iCOM CWM can control up to 16 Chillers and 32 indoor chilled water units belonging to the same system” | “Chiller Teamwork optimization both in constant and variable flow” | not stated未披露 | not stated未披露 | not stated未披露 | Datasheet revision 0, December 2021. It describes an optimisation algorithm that coordinates indoor units with chiller set point and water flow, but not as AI, machine learning or a model, so the optimisation column is not marked. Chiller water flow counts under the plant column here.数据表为 2021 年 12 月第 0 版。描述了一个协调室内机组与冷机设定点和水流量的优化算法,但未称 AI、机器学习或模型,所以优化列未标记。冷机水流量在这里归入冷站列。 |