Products产品

Which products can deliver, who makes them, and when does the next generation arrive?哪些产品能交付、谁在做、下一代什么时候来?

Over the next three years, warm facility water reorganises the AI plant.未来三年,温水重组 AI 冷站。

Dry coolers take the base load and chillers become trim.干冷器承担基载,冷机变成补冷。

103 entries in seven categories; evidence checked 2026-10-12 to 2026-10-17七个类别 103 条;证据核查 2026-10-12 至 2026-10-17

IT sideIT 侧取热
Facility side设施侧排热
System map: where the heat goes on the chosen routes系统图:所选路线上热量的去向
Chip and package芯片与封装Rack机柜(二次侧)CDU or terminalCDU 或末端Plant冷站(设施水)Outdoor室外排热 GPU / CPU packageGPU / CPU 封装 GPU roadmap →GPU 路线图 → Server fans, containment服务器风扇、封闭通道 Cold plates冷板 7 entries tracked已跟踪 7 条 Manifolds and QDs分水器、快接头 4 entries tracked已跟踪 4 条 Rear-door heat exchanger背板换热器 13 entries tracked已跟踪 13 条 Immersion tank浸没槽 CRAH, fan wall精密空调、风墙 11 entries tracked已跟踪 11 条 In-row cooler列间空调 Liquid-to-liquid CDU液-液 CDU 17 entries tracked已跟踪 17 条 Liquid-to-air CDU液-气 CDU 1 entry tracked已跟踪 1 条 Two-phase CDU (condenser)两相 CDU(冷凝器) Pumps水泵 13 entries tracked已跟踪 13 条 Water-cooled chiller水冷冷机 8 entries tracked已跟踪 8 条 Plate heat exchanger板式换热器 Air-cooled chiller风冷冷机 10 entries tracked已跟踪 10 条 Cooling tower冷却塔 Dry cooler干冷器 12 entries tracked已跟踪 12 条 Adiabatic or hybrid cooler绝热或混合干冷器 7 entries tracked已跟踪 7 条 Heat reuse, heat pump热回收、热泵 Facility water class (ASHRAE): 设施水温等级(ASHRAE):W17 W27 W32 W40 W45 W+ Controls run across every layer控制系统贯穿各层
  1. Chip and package芯片与封装
  2. Rack机柜(二次侧)
  3. CDU or terminalCDU 或末端
  4. Plant冷站(设施水)
  5. Outdoor室外排热

Moving line: the main heat path. Dotted: an alternative to that step. Dashed: a conditional step (chiller trim on hot hours). Not every pair is a sensible design: air routes usually need colder water than a dry cooler alone can supply. T6 shows single-phase immersion; two-phase immersion condenses its vapour on a coil in the tank.流动线:主要热量路径。点线:该步骤的替代选项。虚线:有条件的步骤(热天冷机补冷)。并非每种组合都合理:风冷路线通常需要比单靠干冷器更低的水温。T6 图示单相浸没;两相浸没在槽内盘管上冷凝蒸汽。

Counts come from the published deep-dive matrices. Nodes without a count are not covered yet.数量来自已发布深挖页的矩阵。没有数量的节点尚未覆盖。

103

Entries in the seven deep-dive matrices on the map: cold plates and manifolds, rear doors, fan walls, CDUs, pumps and drives, chillers and dry coolers系统图上七个深挖矩阵的条目:冷板和分水器、背板、风墙、CDU、水泵和变频器、冷机、干冷器

One product line, model or part family each每条为一个产品系列、型号或部件族
37

Makers with public product lines or timeline events in the evidence base证据底座中有公开产品线或时间轴事件的厂商

Company index below见下方公司索引
28

Stated plans on the master timeline, out of 177 events总时间轴上公司公布的计划,共 177 个事件

Plans stay plans until confirmed确认前一直标为计划

Equipment categories设备类别

In-rack liquid parts机柜内液冷部件

Over the next three years the in-rack parts decide whether warm water reaches the chip.未来三年,机柜内部件决定暖水能否到达芯片。

Layer: Rack层级:机柜(二次侧)11 entries11 条

Rear-door heat exchangers背板换热器

No rear door here shows a W32–W45 rating. In a warm-water AI plant, a door needs separate selection or its own colder loop; it suits 20–⁠50 kW retrofits, not the main heat path.这里没有一款背板给出 W32–W45 水下的额定值。在温水 AI 冷站里,背板要单独选型或配自己的较冷回路;它适合 20–⁠50 kW 的改造,而不是主散热路径。

Layer: Rack层级:机柜(二次侧)13 entries13 条

CDUCDU

Over the next three years, the biggest change for CDUs is not size but water temperature.未来三年,CDU 最大的变化不是单机变大,而是水温变高。

Layer: CDU or terminal层级:CDU 或末端18 entries18 条

Fan walls风墙

Fan walls are rated on water near 20 °C. In a warm-water AI plant they become the air half of a two-temperature plant, fed by a colder branch.风墙按约 20 °C 的水标定额定值。在温水 AI 冷站里,它是双温冷站中空气的那一半,由一条较冷支路供水。

Layer: CDU or terminal层级:CDU 或末端11 entries11 条

Chillers冷水机组

Over the next three years, the chiller in AI data centers moves from base load to trim.未来三年,冷水机组在 AI 数据中心里的角色会从基础负荷变成补充调峰。

Layer: Plant层级:冷站(设施水)18 entries18 条

Pumps and drives水泵与变频器

All three makers offer variable speed in two forms. Drives built into the pump are stated up to 22–⁠55 kW (Armstrong to 450 hp); larger plant pumps use separate drives.三家都提供两种变频方式。一体式驱动写明到 22–⁠55 kW(Armstrong 到 450 hp);更大的冷站水泵配独立变频器。

Layer: Plant层级:冷站(设施水)13 entries13 条

Dry coolers干冷器

Over the next three years, the dry cooler becomes the AI plant's base-load machine.未来三年,干冷器会成为 AI 冷站的基础负荷设备。

Layer: Outdoor层级:室外排热19 entries19 条

Cooling controls冷却控制

Most controls cover one or two cooling layers. The missing link for AI sites, between fast-swinging IT load and the plant, is stated by only one offering and trialled by one more.多数控制产品只管冷却链的一到两个层级。AI 站点缺的是快速波动的 IT 负载与冷站之间的那一环:只有一家写明做到,另有一项试验以此为目标。

14 entries14 条

Company coverage on the heat path热路径上的公司覆盖

Which listed companies supply each step from the chip to the outdoors. 51 of 67 placements are backed by an official company source; the others are marked as preliminary.从芯片到室外,每一步由哪些上市公司供货。67 个归类中 51 个有公司官方来源,其余标为初步归类。

Reviewed 2026-10-122026-10-12 复核
Master timeline, 2023 Q4 to 2029 Q3: chips and racks above, thermal equipment below总时间轴,2023 年第四季度至 2029 年第三季度:上为芯片与机柜,下为热管理设备
202420252026202720282029Chips and racks (demand)芯片与机柜(需求)Thermal equipment (supply)热管理设备(供给) NVIDIANVIDIAAMDAMDGoogleGoogleAWSAWSMicrosoftMicrosoftMetaMetaHuaweiHuaweiIntelIntelCDUCDUChillers冷机Dry coolers干冷器In-rack parts机柜内部件Rear doors背板Fan walls风墙Controls控制Pumps水泵Immersion浸没
'24'25'26'27'28'29Chips and racks (demand)芯片与机柜(需求)Thermal equipment (supply)热管理设备(供给) NVIDIANVIDIAAMDAMDGoogleGoogleAWSAWSMicrosoftMicrosoftMetaMetaHuaweiHuaweiIntelIntelCDUCDUChillers冷机Dry coolers干冷器In-rack parts机柜内部件Rear doors背板Fan walls风墙Controls控制Pumps水泵Immersion浸没
Filled dot: happened on a known day or month. Filled bar: happened, known only to the year. Hollow dot with a dashed line: a stated plan over its window; a hollow dot alone: a plan with a loose window such as "early 2027". A plan stays a plan until a source confirms it happened. Superseded targets are left out. Every event, with its sources, is in the table view.实心点:已发生,日期或月份已知。实心条:已发生,只知道年份。空心点加虚线:公司公布的计划及其时间窗口;只有空心点:窗口较宽松的计划,例如"2027 年初"。在有来源确认发生前一直是计划。被替代的旧目标不显示。每个事件及来源见"表"视图。

Dated editions, kept as published: 原样保留的历史版本:product charts of 2026-10-07 (eight charts, PDF and ZIP)2026-10-07 产品图表(八张图、PDF 和 ZIP); ;earlier research edition早期研究版.

Components and supporting equipment: sourced lists部件与配套设备:有来源的名单

Checked 2026-10-15. Company materials, plus press reports where marked; ratings as the company states them, with the conditions it leaves out. Not a market-share ranking.2026-10-15 核查。使用公司资料,另有注明的媒体转述;额定值按公司表述,并注明其缺失的工况。不是市场份额排名。
Rear-door heat exchangers背板换热器 Rack机柜 3 entries3 条
Company公司Product family产品系列As stated, and what is missing公司表述及缺失信息Source wording来源原文
VertivLiebert DCD rear-door heat exchangerLiebert DCD 背板换热器Up to 50 kW (family heading); water temperature for that rating not stated.最高 50 kW(产品系列标题);该额定值对应的水温未写明。 Vendor claim厂商说法Liebert® DCD Water Based Cooling Modules up to 50 kW source来源
Motivair (Schneider Electric)ChilledDoor active rear-door heat exchangerChilledDoor 主动式背板换热器Up to 75 kW per rack with 100% heat removal; water temperature and airflow not stated.每机柜最高 75 kW,100% 排热;水温和风量未写明。 Vendor claim厂商说法an active rear door heat exchanger capable of removing server densities up to 75kW per rack and 100% heat removal. source来源
API Heat TransferRear Door Cooler (active)Rear Door Cooler(主动式背板)Up to 75 kW per rack; rating conditions not read.每机柜最高 75 kW;未读到额定工况。 Vendor claim厂商说法Designed for high-density cooling up to 75kW per rack. source来源
Fan walls and chilled-water CRAH风墙和冷冻水精密空调 Room机房 5 entries5 条
Company公司Product family产品系列As stated, and what is missing公司表述及缺失信息Source wording来源原文
TraneFan Coil Wall for Data Centers数据中心风机盘管墙(Fan Coil Wall)400 kW or more per unit (headline); water temperatures not stated with the headline.每台 400 kW 以上(标题数字);未同时写明水温。 Vendor claim厂商说法Delivers proven, mission-critical performance—with 400kW or greater cooling capacity source来源
Daikin AppliedPro-W fan wallPro-W 风墙200–700 kW, chilled-water coil with EC fans; rating conditions not stated.200–700 kW,冷冻水盘管配 EC 风机;额定工况未写明。 Vendor claim厂商说法Model ranges from 200kW to 700kW cooling capacity source来源
Johnson ControlsData-centre air handling (YORK CRAH and Silent-Aire)数据中心空气处理设备(YORK 精密空调和 Silent-Aire)55–800 kW (8,000–90,000 CFM); the page does not tie this range clearly to one line; conditions not stated.55–800 kW(8,000–90,000 CFM);页面未明确该范围对应哪条产品线;工况未写明。 Vendor claim厂商说法Sizes from 55kW to 800kW (8K to 90K CFM) source来源
STULZCyberAir 3PRO CW (chilled-water CRAH)CyberAir 3PRO CW(冷冻水精密空调)22–260 kW; rating conditions not stated.22–260 kW;额定工况未写明。 Vendor claim厂商说法Cooling capacity (kW): 22 – 260 source来源
Envicool China中国CyberMate precision cooling unitsCyberMate 精密空调Direct expansion 6–120 kW; chilled water 40–200 kW (from the catalogue model-code table); rating conditions not captured.直膨 6–120 kW;冷冻水 40–200 kW(取自样本型号编码表);未取得额定工况。 Vendor claim厂商说法DX: 6-120kW … CW: 40-200kW source来源
Plate heat exchangers for CDUsCDU 用板式换热器 CDUCDU 3 entries3 条
Company公司Product family产品系列As stated, and what is missing公司表述及缺失信息Source wording来源原文
DanfossB3-260C brazed plate heat exchanger for CDUsB3-260C CDU 用钎焊板式换热器Up to 1 MW, and designed for log-mean temperature differences of about 2 K; the page does not say these apply at the same operating point, and gives no flow, water temperatures or pressure drop. Launched 2026-02-09.最高 1 MW,按约 2 K 的对数平均温差设计;页面未说明两者是否为同一工况,也未给出流量、进出水温度或压降。2026-02-09 发布。 Vendor claim厂商说法With capacities up to 1 MW … optimized for very low Log Mean Temperature Difference (LMTD) applications (~2 K) source来源
Alfa LavalHeat exchangers in Boyd's in-row CDUBoyd 列间 CDU 中的换热器The Boyd in-row CDU built with Alfa Laval gives up to 2.3 MW; the exchanger model, flow, water temperatures, approach and pressure drop are not stated.与 Alfa Laval 合作的 Boyd 列间 CDU 最高 2.3 MW;未写换热器型号、流量、水温、接近温差和压降。 Vendor claim厂商说法up to 2.3 MW source来源
KelvionGasketed plate heat exchangers and coolant distribution units (CCDUs)垫片式板式换热器和冷却液分配单元(CCDU)No ratings on the page.页面无额定数据。 Vendor claim厂商说法Direct cooling of components with non-conductive liquids enables greater heat absorption source来源
Quick disconnects快接头 Rack机柜 1 entry1 条
Company公司Product family产品系列As stated, and what is missing公司表述及缺失信息Source wording来源原文
Danfoss (Danfoss Hansen)UQD, UQDB and MQD couplingsUQD、UQDB 和 MQD 接头UQDB blind-mate coupling with 1 mm radial self-alignment; size -04 available, -02, -06 and -08 listed as coming soon on this page.UQDB 盲插接头,径向自对中 1 mm;本页显示 -04 规格已有,-02、-06、-08 标为即将推出。 Vendor claim厂商说法self- alignment feature with radial compensation of 1 mm source来源
Coolants冷却液 Rack and CDU机柜与 CDU 2 entries2 条
Company公司Product family产品系列As stated, and what is missing公司表述及缺失信息Source wording来源原文
CastrolON direct-to-chip (PG 25) and immersion fluidsON 芯片直接液冷(PG 25)和浸没液No ratings on the category page.品类页无额定数据。 Vendor claim厂商说法dissipating heat directly from critical electronic components source来源
FuchsRENOLIN FECC single-phase immersion fluidsRENOLIN FECC 单相浸没液Synthetic dielectric fluids for single-phase immersion; one grade listed as OCP Accepted.单相浸没用合成介电液;其中一个牌号标为 OCP Accepted。 Vendor claim厂商说法RENOLIN FECC 5 SYNTH Iceotope OCP Accepted™ Immersion Requirements Rev 2.1 source来源
Pumps水泵 CDU and plantCDU 与冷站 4 entries4 条
Company公司Product family产品系列As stated, and what is missing公司表述及缺失信息Source wording来源原文
WiloStratos GIGA B with IE5 motorsStratos GIGA B(IE5 电机)IE5 motors in operation at Iron Mountain, Haarlem; flow and head not stated.Iron Mountain 哈勒姆数据中心运行 IE5 电机水泵;流量和扬程未写明。 Vendor claim厂商说法Wilo-Stratos GIGA B pumps with IE5 motors are in operation source来源
Xylem (Bell & Gossett)Smart variable-speed pumps (e-SV, e-HM, ecocirc XL and others)智能变速水泵(e-SV、e-HM、ecocirc XL 等)Pumps from cooling towers to direct-to-chip loops; the page does not say which goes in a CDU.从冷却塔到芯片直接液冷回路的水泵;页面未说明哪种用于 CDU。 Vendor claim厂商说法cooling towers to direct-to-chip liquid cooling systems source来源
KSBEtanorm and Etabloc pumps with PumpDriveEtanorm 和 Etabloc 水泵配 PumpDrive 变频器Room-cooling water circuits, not CDUs: 24 pump sets and 413 valves at SAP St. Leon-Rot.机房冷却水系统,不是 CDU:SAP St. Leon-Rot 项目 24 套泵组、413 个阀门。 Vendor case study厂商案例413 valves and 24 pump sets source来源
Armstrong Fluid TechnologyDesign Envelope pumps and EVERCOOL plant controlDesign Envelope 水泵和 EVERCOOL 冷站控制EVERCOOL cuts site commissioning time by up to 30% (vendor claim, no baseline).EVERCOOL 将现场调试时间缩短最多 30%(厂商说法,无基准)。 Vendor claim厂商说法reducing site commissioning time by up to 30% source来源
Oil-free centrifugal compressors无油离心压缩机 Plant冷站 2 entries2 条
Company公司Product family产品系列As stated, and what is missing公司表述及缺失信息Source wording来源原文
DanfossTurbocor VTT magnetic-bearing centrifugal compressorTurbocor VTT 磁悬浮离心压缩机200–400 tons (700–1,430 kW) nominal with R134a; the evaporating and condensing temperatures behind the nominal rating are not stated. Marketed for 24/7 buildings such as data centres.名义 200–400 冷吨(700–1,430 kW),R134a;未写名义工况对应的蒸发和冷凝温度。面向数据中心等全天运行建筑。 Vendor claim厂商说法nominal capacity ranges from 200 to 400 Tons (700 to 1430 kW) source来源
CopelandOil-free centrifugal compressor with Aero-lift bearings (not magnetic)采用 Aero-lift 轴承的无油离心压缩机(非磁悬浮)Being developed for 50–200 tons (March 2024 release); the bearing works without electromagnetics, shown for comparison with magnetic bearings.按 50–200 冷吨开发(2024 年 3 月发布);轴承不依赖电磁,用于与磁悬浮对比。 Vendor claim厂商说法frictionless Aero-lift™ bearing technology source来源
EC fansEC 风机 Room and outdoor机房与室外 2 entries2 条
Company公司Product family产品系列As stated, and what is missing公司表述及缺失信息Source wording来源原文
RosenbergEC axial fans for recoolers, chillers and cooling towers用于干冷器、冷机和冷却塔的 EC 轴流风机850 EC axial fans on one Texas data-centre roof.得州一座数据中心屋顶装有 850 台 EC 轴流风机。 Vendor claim厂商说法850 EC axial fans provide reliable and energy-efficient cooling source来源
ebm-papstRadiFlow 630 fan for CRAH and fan-wall units用于精密空调和风墙机组的 RadiFlow 630 风机Up to 10% more efficient than competitors in the application (vendor claim; baseline not stated).在应用中效率比竞品最高高 10%(厂商说法;未写比较基准)。 Vendor claim厂商说法 Reported by trade press行业媒体转述delivering up to 10% higher efficiency in the application compared with market competitors source来源
Plant and white-space controls冷站与机房控制 All layers各层 5 entries5 条
Company公司Product family产品系列As stated, and what is missing公司表述及缺失信息Source wording来源原文
VertivLiebert iCOM unit control and teamworkLiebert iCOM 机组控制与群控Networked cooling units work as one system; efficiency gain of 28–40% (vendor claim, no baseline).联网的冷却机组作为一个系统运行;效率提升 28–40%(厂商说法,无基准)。 Vendor claim厂商说法Intelligent controls allow you to recover energy that would be wasted due to unit “fighting,” improving efficiency by 28 to 40 percent source来源
Johnson ControlsOpenBlue chilled-water plant optimisationOpenBlue 冷冻水站优化One UK financial-services data centre: chilled-plant efficiency up 8%, PUE 1.296, 355,000 kWh a year saved.英国一家金融服务数据中心:冷站效率提升 8%,PUE 1.296,每年节电 355,000 kWh。 Vendor case study厂商案例8% increase in chilled plant energy efficiency source来源
TraneTracer chiller plant controlTracer 冷站控制Chiller staging and sequencing, pump pressure reset, chilled-water reset, free cooling, heat recovery and storage; no quantified saving.冷机台数控制与轮换、水泵压差重设、冷冻水温重设、自然冷却、热回收和蓄冷;未给出量化节能。 Vendor claim厂商说法Chiller plant control manages the rotation, staging and sequencing of multiple chillers. source来源
Schneider ElectricEcoStruxure IT Cooling Optimize (white space only)EcoStruxure IT Cooling Optimize(仅机房白区)Adjusts CRAC/CRAH airflow in real time; customers saw on average 10% lower PUE and 38% lower cooling power (vendor claim).实时调节精密空调风量;厂商称客户平均 PUE 降低 10%、冷却用电降低 38%(厂商说法)。 Vendor claim厂商说法10% reduction in PUE 38% reduction in cooling system power usage source来源
SiemensDesigo CC with White Space Cooling OptimizationDesigo CC 配白区冷却优化Contributes to a target PUE of 1.2 at a new Tallinn data centre (a target, not a measurement).有助于塔林新数据中心实现 PUE 1.2 的目标(为目标值,不是实测)。 Vendor claim厂商说法contributing to its target Power Usage Effectiveness (PUE) value of 1.2 source来源
What is not covered: 未覆盖:Few Chinese or Taiwanese makers are listed: their own pages could not be reached, so broker and press lists were not used. Several large makers (Grundfos, Stäubli, CPC, Parker, Shell, Dow, Legrand USystems, Hanbell, Midea) blocked automated reading and are left out until their pages are opened. Most air-handler and rear-door ratings lack the water temperatures they apply to.中国大陆和台湾厂商列得很少:无法打开其官网,因此未使用券商和媒体名单。若干大厂(Grundfos、Stäubli、CPC、Parker、Shell、Dow、Legrand USystems、汉钟、美的)的页面无法自动读取,在打开其官网前暂不列入。多数空气处理机组和背板的额定值缺少对应水温。
Company index: makers with public product lines or events in the evidence base公司索引:证据底座中有公开产品线或事件的厂商37 rows37 行
Showing显示 37Listing comes from the 21-company registry; other makers are tracked by name only.上市信息来自 21 家公司注册表;其他厂商只按名称跟踪。
Company公司Public product lines公开产品线Categories类别Events on the timeline时间轴事件Listing上市
Vertiv11CDU, Chiller, Dry cooler, In-rack, Rear door, Fan wall, Controls12NYSE: VRT
Trane8CDU, Chiller, Dry cooler, Immersion, Fan wall, Controls13NYSE: TT
Modine7CDU, Chiller, Dry cooler, Fan wall12NYSE: MOD
Schneider Electric6CDU, Chiller, Rear door, Fan wall, Controls11Euronext Paris: SU
Daikin6CDU, Chiller, In-rack, Controls, Fan wall9Tokyo Stock Exchange: 6367
Carrier6CDU, Chiller, Dry cooler, Fan wall, Controls8NYSE: CARR
Delta5CDU, In-rack, Rear door, Controls5TWSE: 2308
Johnson Controls6CDU, Chiller, Fan wall, Controls3NYSE: JCI
Envicool4CDU, In-rack4SZSE: 002837
Huawei2Fan wall, Controls5○
Mitsubishi Electric4Chiller, Fan wall3○
STULZ7CDU, Chiller, Fan wall, Rear door, Controls○
AMD6○
nVent5CDU, In-rack, Rear door, Controls1NYSE: NVT
NVIDIA6○
Grundfos5Pump, Pump drive○
Munters2Dry cooler3Nasdaq Stockholm: MTRS
Armstrong4Pump, Pump drive○
CoolIT4CDU, In-rack, Controls○
Google4Nasdaq: GOOGL
Meta4Nasdaq: META
Wilo4Pump, Pump drive○
AWS3Nasdaq: AMZN
Shenling3CDU, Chiller, Dry coolerSZSE: 301018
BAC2Dry cooler○
EVAPCO2Dry cooler○
GRC1Immersion1○
Güntner2Dry cooler○
Intel2○
Kelvion2Dry cooler○
LU-VE2Dry cooler○
Microsoft2Nasdaq: MSFT
Submer1Immersion1○
Alfa Laval1Dry cooler○
Auras1TPEx: 3324
Boyd1In-rack○
Cooler Master1In-rack○
Database view: components and supporting equipment, with source wording数据库视图:部件与配套设备及来源原文27 rows27 行
Showing显示 27Ratings are the companies' own, with missing conditions stated. Quotes are the source's own wording, checked against the source text.额定值为公司自己的数字,并注明缺失的工况。引文为来源原文,已与来源文本核对。
Group类别Position位置Company公司Product family产品系列As stated公司表述Kind类型Source wording来源原文Source来源
Rear-door heat exchangers背板换热器Rack机柜VertivLiebert DCD rear-door heat exchangerLiebert DCD 背板换热器Up to 50 kW (family heading); water temperature for that rating not stated.最高 50 kW(产品系列标题);该额定值对应的水温未写明。Vendor claim厂商说法Liebert® DCD Water Based Cooling Modules up to 50 kWlink链接
Rear-door heat exchangers背板换热器Rack机柜Motivair (Schneider Electric)ChilledDoor active rear-door heat exchangerChilledDoor 主动式背板换热器Up to 75 kW per rack with 100% heat removal; water temperature and airflow not stated.每机柜最高 75 kW,100% 排热;水温和风量未写明。Vendor claim厂商说法an active rear door heat exchanger capable of removing server densities up to 75kW per rack and 100% heat removal.link链接
Rear-door heat exchangers背板换热器Rack机柜API Heat TransferRear Door Cooler (active)Rear Door Cooler(主动式背板)Up to 75 kW per rack; rating conditions not read.每机柜最高 75 kW;未读到额定工况。Vendor claim厂商说法Designed for high-density cooling up to 75kW per rack.link链接
Fan walls and chilled-water CRAH风墙和冷冻水精密空调Room机房TraneFan Coil Wall for Data Centers数据中心风机盘管墙(Fan Coil Wall)400 kW or more per unit (headline); water temperatures not stated with the headline.每台 400 kW 以上(标题数字);未同时写明水温。Vendor claim厂商说法Delivers proven, mission-critical performance—with 400kW or greater cooling capacitylink链接
Fan walls and chilled-water CRAH风墙和冷冻水精密空调Room机房Daikin AppliedPro-W fan wallPro-W 风墙200–700 kW, chilled-water coil with EC fans; rating conditions not stated.200–700 kW,冷冻水盘管配 EC 风机;额定工况未写明。Vendor claim厂商说法Model ranges from 200kW to 700kW cooling capacitylink链接
Fan walls and chilled-water CRAH风墙和冷冻水精密空调Room机房Johnson ControlsData-centre air handling (YORK CRAH and Silent-Aire)数据中心空气处理设备(YORK 精密空调和 Silent-Aire)55–800 kW (8,000–90,000 CFM); the page does not tie this range clearly to one line; conditions not stated.55–800 kW(8,000–90,000 CFM);页面未明确该范围对应哪条产品线;工况未写明。Vendor claim厂商说法Sizes from 55kW to 800kW (8K to 90K CFM)link链接
Fan walls and chilled-water CRAH风墙和冷冻水精密空调Room机房STULZCyberAir 3PRO CW (chilled-water CRAH)CyberAir 3PRO CW(冷冻水精密空调)22–260 kW; rating conditions not stated.22–260 kW;额定工况未写明。Vendor claim厂商说法Cooling capacity (kW): 22 – 260link链接
Fan walls and chilled-water CRAH风墙和冷冻水精密空调Room机房EnvicoolCyberMate precision cooling unitsCyberMate 精密空调Direct expansion 6–120 kW; chilled water 40–200 kW (from the catalogue model-code table); rating conditions not captured.直膨 6–120 kW;冷冻水 40–200 kW(取自样本型号编码表);未取得额定工况。Vendor claim厂商说法DX: 6-120kW … CW: 40-200kWlink链接
Plate heat exchangers for CDUsCDU 用板式换热器CDUCDUDanfossB3-260C brazed plate heat exchanger for CDUsB3-260C CDU 用钎焊板式换热器Up to 1 MW, and designed for log-mean temperature differences of about 2 K; the page does not say these apply at the same operating point, and gives no flow, water temperatures or pressure drop. Launched 2026-02-09.最高 1 MW,按约 2 K 的对数平均温差设计;页面未说明两者是否为同一工况,也未给出流量、进出水温度或压降。2026-02-09 发布。Vendor claim厂商说法With capacities up to 1 MW … optimized for very low Log Mean Temperature Difference (LMTD) applications (~2 K)link链接
Plate heat exchangers for CDUsCDU 用板式换热器CDUCDUAlfa LavalHeat exchangers in Boyd's in-row CDUBoyd 列间 CDU 中的换热器The Boyd in-row CDU built with Alfa Laval gives up to 2.3 MW; the exchanger model, flow, water temperatures, approach and pressure drop are not stated.与 Alfa Laval 合作的 Boyd 列间 CDU 最高 2.3 MW;未写换热器型号、流量、水温、接近温差和压降。Vendor claim厂商说法up to 2.3 MWlink链接
Plate heat exchangers for CDUsCDU 用板式换热器CDUCDUKelvionGasketed plate heat exchangers and coolant distribution units (CCDUs)垫片式板式换热器和冷却液分配单元(CCDU)No ratings on the page.页面无额定数据。Vendor claim厂商说法Direct cooling of components with non-conductive liquids enables greater heat absorptionlink链接
Quick disconnects快接头Rack机柜Danfoss (Danfoss Hansen)UQD, UQDB and MQD couplingsUQD、UQDB 和 MQD 接头UQDB blind-mate coupling with 1 mm radial self-alignment; size -04 available, -02, -06 and -08 listed as coming soon on this page.UQDB 盲插接头,径向自对中 1 mm;本页显示 -04 规格已有,-02、-06、-08 标为即将推出。Vendor claim厂商说法self- alignment feature with radial compensation of 1 mmlink链接
Coolants冷却液Rack and CDU机柜与 CDUCastrolON direct-to-chip (PG 25) and immersion fluidsON 芯片直接液冷(PG 25)和浸没液No ratings on the category page.品类页无额定数据。Vendor claim厂商说法dissipating heat directly from critical electronic componentslink链接
Coolants冷却液Rack and CDU机柜与 CDUFuchsRENOLIN FECC single-phase immersion fluidsRENOLIN FECC 单相浸没液Synthetic dielectric fluids for single-phase immersion; one grade listed as OCP Accepted.单相浸没用合成介电液;其中一个牌号标为 OCP Accepted。Vendor claim厂商说法RENOLIN FECC 5 SYNTH Iceotope OCP Accepted™ Immersion Requirements Rev 2.1link链接
Pumps水泵CDU and plantCDU 与冷站WiloStratos GIGA B with IE5 motorsStratos GIGA B(IE5 电机)IE5 motors in operation at Iron Mountain, Haarlem; flow and head not stated.Iron Mountain 哈勒姆数据中心运行 IE5 电机水泵;流量和扬程未写明。Vendor claim厂商说法Wilo-Stratos GIGA B pumps with IE5 motors are in operationlink链接
Pumps水泵CDU and plantCDU 与冷站Xylem (Bell & Gossett)Smart variable-speed pumps (e-SV, e-HM, ecocirc XL and others)智能变速水泵(e-SV、e-HM、ecocirc XL 等)Pumps from cooling towers to direct-to-chip loops; the page does not say which goes in a CDU.从冷却塔到芯片直接液冷回路的水泵;页面未说明哪种用于 CDU。Vendor claim厂商说法cooling towers to direct-to-chip liquid cooling systemslink链接
Pumps水泵CDU and plantCDU 与冷站KSBEtanorm and Etabloc pumps with PumpDriveEtanorm 和 Etabloc 水泵配 PumpDrive 变频器Room-cooling water circuits, not CDUs: 24 pump sets and 413 valves at SAP St. Leon-Rot.机房冷却水系统,不是 CDU:SAP St. Leon-Rot 项目 24 套泵组、413 个阀门。Vendor case study厂商案例413 valves and 24 pump setslink链接
Pumps水泵CDU and plantCDU 与冷站Armstrong Fluid TechnologyDesign Envelope pumps and EVERCOOL plant controlDesign Envelope 水泵和 EVERCOOL 冷站控制EVERCOOL cuts site commissioning time by up to 30% (vendor claim, no baseline).EVERCOOL 将现场调试时间缩短最多 30%(厂商说法,无基准)。Vendor claim厂商说法reducing site commissioning time by up to 30%link链接
Oil-free centrifugal compressors无油离心压缩机Plant冷站DanfossTurbocor VTT magnetic-bearing centrifugal compressorTurbocor VTT 磁悬浮离心压缩机200–400 tons (700–1,430 kW) nominal with R134a; the evaporating and condensing temperatures behind the nominal rating are not stated. Marketed for 24/7 buildings such as data centres.名义 200–400 冷吨(700–1,430 kW),R134a;未写名义工况对应的蒸发和冷凝温度。面向数据中心等全天运行建筑。Vendor claim厂商说法nominal capacity ranges from 200 to 400 Tons (700 to 1430 kW)link链接
Oil-free centrifugal compressors无油离心压缩机Plant冷站CopelandOil-free centrifugal compressor with Aero-lift bearings (not magnetic)采用 Aero-lift 轴承的无油离心压缩机(非磁悬浮)Being developed for 50–200 tons (March 2024 release); the bearing works without electromagnetics, shown for comparison with magnetic bearings.按 50–200 冷吨开发(2024 年 3 月发布);轴承不依赖电磁,用于与磁悬浮对比。Vendor claim厂商说法frictionless Aero-lift™ bearing technologylink链接
EC fansEC 风机Room and outdoor机房与室外RosenbergEC axial fans for recoolers, chillers and cooling towers用于干冷器、冷机和冷却塔的 EC 轴流风机850 EC axial fans on one Texas data-centre roof.得州一座数据中心屋顶装有 850 台 EC 轴流风机。Vendor claim厂商说法850 EC axial fans provide reliable and energy-efficient coolinglink链接
EC fansEC 风机Room and outdoor机房与室外ebm-papstRadiFlow 630 fan for CRAH and fan-wall units用于精密空调和风墙机组的 RadiFlow 630 风机Up to 10% more efficient than competitors in the application (vendor claim; baseline not stated).在应用中效率比竞品最高高 10%(厂商说法;未写比较基准)。Vendor claim厂商说法; reported by trade press;行业媒体转述delivering up to 10% higher efficiency in the application compared with market competitorslink链接
Plant and white-space controls冷站与机房控制All layers各层VertivLiebert iCOM unit control and teamworkLiebert iCOM 机组控制与群控Networked cooling units work as one system; efficiency gain of 28–40% (vendor claim, no baseline).联网的冷却机组作为一个系统运行;效率提升 28–40%(厂商说法,无基准)。Vendor claim厂商说法Intelligent controls allow you to recover energy that would be wasted due to unit “fighting,” improving efficiency by 28 to 40 percentlink链接
Plant and white-space controls冷站与机房控制All layers各层Johnson ControlsOpenBlue chilled-water plant optimisationOpenBlue 冷冻水站优化One UK financial-services data centre: chilled-plant efficiency up 8%, PUE 1.296, 355,000 kWh a year saved.英国一家金融服务数据中心:冷站效率提升 8%,PUE 1.296,每年节电 355,000 kWh。Vendor case study厂商案例8% increase in chilled plant energy efficiencylink链接
Plant and white-space controls冷站与机房控制All layers各层TraneTracer chiller plant controlTracer 冷站控制Chiller staging and sequencing, pump pressure reset, chilled-water reset, free cooling, heat recovery and storage; no quantified saving.冷机台数控制与轮换、水泵压差重设、冷冻水温重设、自然冷却、热回收和蓄冷;未给出量化节能。Vendor claim厂商说法Chiller plant control manages the rotation, staging and sequencing of multiple chillers.link链接
Plant and white-space controls冷站与机房控制All layers各层Schneider ElectricEcoStruxure IT Cooling Optimize (white space only)EcoStruxure IT Cooling Optimize(仅机房白区)Adjusts CRAC/CRAH airflow in real time; customers saw on average 10% lower PUE and 38% lower cooling power (vendor claim).实时调节精密空调风量;厂商称客户平均 PUE 降低 10%、冷却用电降低 38%(厂商说法)。Vendor claim厂商说法10% reduction in PUE 38% reduction in cooling system power usagelink链接
Plant and white-space controls冷站与机房控制All layers各层SiemensDesigo CC with White Space Cooling OptimizationDesigo CC 配白区冷却优化Contributes to a target PUE of 1.2 at a new Tallinn data centre (a target, not a measurement).有助于塔林新数据中心实现 PUE 1.2 的目标(为目标值,不是实测)。Vendor claim厂商说法contributing to its target Power Usage Effectiveness (PUE) value of 1.2link链接