Can a dry cooler make the 41 °C facility water of NVIDIA's reference example?干冷器能造出 NVIDIA 参考示例中 41 °C 的设施水吗?

Over the next three years, the dry cooler becomes the AI plant's base-load machine.未来三年,干冷器会成为 AI 冷站的基础负荷设备。

Evidence checked 2026-10-13, reviewed monthly证据核查 2026-10-13,每月复核

What the catalogues state: 19 dry and adiabatic lines样本里写了什么:19 个干式与绝热系列
Capacity tied to fluid and air temperatures容量与液温和气温挂钩 3 of 1919 个中 3 个Capacity or range without conditions只有容量或范围,没有工况 14 of 1919 个中 14 个No capacity stated未写容量 2 of 1919 个中 2 个
Capacity tied to容量与液温和 3 of 1919 个中 3 个Capacity or range只有容量或范 14 of 1919 个中 14 个No capacity stated未写容量 2 of 1919 个中 2 个
Dry coolers are sized in vendor selection software; a catalogue kilowatt without fluid and air temperatures cannot be compared. None of the three rated points is a complete single-unit rating.干冷器通过厂商选型软件配置;没有液温和气温的样本千瓦数无法比较。三个有工况的点都不是完整的单机额定值。
3of 19

Lines that tie a capacity to fluid and air temperatures把容量与液温和气温挂钩的系列

Catalogues and datasheets样本和数据表Full matrix完整矩阵
31–35.4°C

Air at or below which the two points with a leaving temperature could still make 41 °C water: Kelvion 31 °C (approach 10 K), Baltimore Aircoil (BAC) 35.4 °C (approach 5.6 K)两个写明出液温度的点,在不高于此气温时仍可造出 41 °C 的水:Kelvion 31 °C(接近温差 10 K),Baltimore Aircoil (BAC) 35.4 °C(接近温差 5.6 K)

Same approach assumed; a screen, not a rating假设接近温差不变;只是筛查,不是额定值Direct feed to the CDUs assumed假设直接给 CDU 供水KelvionKelvion Baltimore Aircoil (BAC)Baltimore Aircoil (BAC)
1,000+

Dry coolers in Kelvion's announced contract: more than USD 800 million, for 5 GW of project heat-rejection capacity in 2027Kelvion 公布的合同中的干冷器台数:超过 8 亿美元,用于 2027 年 5 GW 的项目排热能力

Company announcement公司公告KelvionKelvion

The owner's judgement作者判断

With 41–45 °C liquid cooling, the dry cooler rejects the plant's heat to outdoor air without a compressor. What do the main dry and adiabatic lines state, and can they make NVIDIA's 41 °C facility water?在 41–45 °C 液冷下,干冷器不用压缩机就能把冷站的热量排到室外空气中。主要的干式和绝热系列标称了什么?它们能造出 NVIDIA 示例的 41 °C 设施水吗?

Willow Lei · judgementWillow Lei · 判断

Over the next three years the dry cooler becomes the base-load machine of the AI plant: Kelvion has announced a contract worth more than USD 800 million to supply over 1,000 dry coolers for 5 GW of project heat-rejection capacity in 2027.

Yet dry coolers are bought on numbers nobody can compare: of 19 lines I checked, only three tie a capacity to fluid and air temperatures, and none of them is a complete single-unit rating.

The condition is ratings at the warm-water point (for example 46/41 °C fluid at 35 °C air) and a climate whose design day stays below that line, or adiabatic assist and its water use; where both hold, the dry cooler replaces the chiller as the plant's main machine.

未来三年,干冷器会成为 AI 冷站的基础负荷设备:Kelvion 宣布了一份超过 8 亿美元的合同,2027 年供应 1,000 多台干冷器,对应 5 GW 的项目排热容量。

但干冷器的采购依据的是无法相互比较的数字:我检查的 19 个系列里,只有三个把容量与液温和气温联系起来,而且没有一个是完整的单台额定值。

条件是厂商公布暖水工况下的额定值(例如 35 °C 空气下 46/41 °C 液温),且当地设计日气温低于这条线,或接受绝热辅助及其用水;两者都满足的地方,干冷器取代冷水机组成为冷站的主机。

Sources: 来源:[1] [2] [3]

Timeline slice: the latest six events that happened, then the stated plans时间轴切片:最近六个已发生事件,然后是公布的计划

Filled dot: happened. Hollow dot and "Planned": a stated plan with its window; it stays a plan until a source confirms it happened. The full six-year roadmap is further down.实心点:已发生。空心点加"计划":公司公布的计划及其时间窗口;在有来源确认发生前一直是计划。完整六年路线图在下方。

The three lines with stated conditions三个写明工况的系列

Rule: every line that ties a capacity to fluid and air temperatures.规则:把容量与液温和气温挂钩的全部系列。

Vertiv Liebert direct-drive drycooler

275 kW; fluid 48.9 / — °C at 35 °C air.275 kW;进 / 出液 48.9 / — °C,空气 35 °C。

Largest standard 60 Hz model; 'Capacity shown is Drycooler THR at sea level'. Leaving fluid temperature not stated. 50 Hz: 242 kW.最大的 60 Hz 标准型号;“容量为海平面处干冷器总排热量”。未写出水温度。50 Hz 时为 242 kW。

Dry干式

Kelvion V-shape dry cooler (LV)

family 6–2,140 kW; fluid 40 / 35 °C at 25 °C air.系列 6–2,140 kW;进 / 出液 40 / 35 °C,空气 25 °C。

Capacity range 6–2,140 kW printed with its conditions directly beneath it: water, tA1 = 25 °C air, tL1 = 40 °C in, tL2 = 35 °C out. A conditioned family range, not one unit's rating.容量范围 6–2,140 kW,下方直接印有工况:水,tA1 = 25 °C 空气,tL1 = 40 °C 进液,tL2 = 35 °C 出液。这是带工况的系列范围,不是单台额定值。
Dry干式

Baltimore Aircoil (BAC) TrilliumSeries TDFS

up to (nominal family maximum) 2,931 kW; fluid 46.1 / 40.6 °C at 35 °C air.最高(系列名义最大值) 2,931 kW;进 / 出液 46.1 / 40.6 °C,空气 35 °C。

'Nominal capacity based on a 115° F EWT and 105° F LWT at a 95° F dry bulb'. The brochure does not say which model reaches 10,000 MBH.“名义容量基于 115°F 进水、105°F 出水、95°F 干球温度”。样本没有说明哪个型号达到 10,000 MBH。

Dry干式

Compare two or three自选两到三款比较

○ = not stated by the vendor. Values keep the vendor's own conditions; they are not a ranking. Choose "—" in the third box to compare two.○ = 厂商未标称。数值保留厂商自己的工况,不构成排名。第三个框选"—"即可只比较两款。

Can a dry cooler make 41 °C water? The engineering reading干冷器能造出 41 °C 的水吗?工程解读

NVIDIA's reference example supplies 41 °C facility water to the CDUs. A dry cooler's leaving fluid sits a few kelvin above the outdoor air (its approach). Engineering reading, not a vendor statement: from each rated point, the air temperature at which that unit could still deliver 41 °C water at the same approach. Approach changes with flow, fan speed and selection, so this is a screen, not a rating. The reading assumes the dry cooler feeds the CDUs directly; with an intermediate heat exchanger, subtract that exchanger's approach as well.NVIDIA 的参考示例给 CDU 供 41 °C 的设施水。干冷器的出液温度比室外空气高几 K(接近温差)。以下是工程解读,不是厂商声明:按每个额定点,估算在相同接近温差下仍能供 41 °C 水的空气温度。接近温差随流量、风机转速和选型而变,因此这只是筛查,不是额定值。该解读假设干冷器直接给 CDU 供水;如有中间换热器,还要再减去该换热器的接近温差。 NVIDIA sourceNVIDIA 来源

Stated point (vendor source)标称工况点(厂商来源)kWEngineering reading工程解读
Vertiv Liebert direct-drive drycooler275leaving fluid not stated; approach cannot be read未写出液温度,无法读出接近温差
Kelvion V-shape dry cooler (LV)range 6–2,140范围 6–2,140leaves 35 °C at 25 °C air (approach 10 K): 41 °C water needs air at or below about 31 °C在 25 °C 空气下出液 35 °C(接近温差 10 K):要得到 41 °C 的水,空气约需不高于 31 °C
Baltimore Aircoil (BAC) TrilliumSeries TDFSup to (nominal family maximum) 最高(系列名义最大值) 2,931leaves 40.6 °C at 35 °C air (approach 5.6 K): 41 °C water needs air at or below about 35.4 °C在 35 °C 空气下出液 40.6 °C(接近温差 5.6 K):要得到 41 °C 的水,空气约需不高于 35.4 °C
Full roadmap 2023 Q4 – 2029 Q3 (13 events), who earns the revenue, and the method完整路线图 2023 年第四季度至 2029 年第三季度(13 个事件)、谁获得收入、方法

Roadmap, 2023 Q4 – 2029 Q3路线图,2023 年第四季度至 2029 年第三季度

Dated events from official sources. Planned events show the window the source states; passing the window does not prove shipment. No future model is inferred.来自官方来源的有日期事件。计划事件显示来源给出的时间窗口;窗口过去并不代表已经出货。不推测未来型号。

Dry and adiabatic coolers for data centers面向数据中心的干冷器与绝热冷却器

  1. Jan 20252025 年 1 月 BAC launches the TrilliumSeries dry coolerBAC 发布 TrilliumSeries 干冷器
  2. Apr 20252025 年 4 月 Kelvion updates its adiabatic spray system: ambient-responsive water control and a VFD pump as standardKelvion 更新绝热喷淋系统:随环境调节用水,标配变频水泵
  3. Feb 20262026 年 2 月 EVAPCO introduces the CTI-certified eco-Air APEX dry cooler for high-density data centersEVAPCO 推出面向高密度数据中心、经 CTI 认证的 eco-Air APEX 干冷器

Contracts and ownership订单与收购

  1. Oct 20242024 年 10 月 Munters completes the Geoclima acquisitionMunters 完成收购 Geoclima
  2. Aug 20262026 年 8 月 SLB agrees to acquire 100% of Kelvion: USD 4.1 billion enterprise valueSLB 同意收购 Kelvion 100% 股权:企业价值 41 亿美元
  3. Oct 20262026 年 10 月 Kelvion announces an AI data-center heat-rejection contract worth more than USD 800 million, for 5 GW of project capacityKelvion 宣布一份 AI 数据中心排热合同,金额超过 8 亿美元,对应 5 GW 项目排热容量
  4. Target through 2027目标 2027 年全年 Kelvion supplies more than 1,000 Mega-Bay dry coolers under that contractKelvion 按该合同供应 1,000 台以上 Mega-Bay 干冷器 announced Oct 20262026 年 10 月公布 planned计划
  5. Target H1 2027目标 2027 年上半年 SLB's acquisition of Kelvion closes, subject to approvalsSLB 完成收购 Kelvion(须获批准) announced Aug 20262026 年 8 月公布 planned计划

Factories工厂

  1. Dec 20242024 年 12 月 LU-VE's expanded Tianmen plant in China becomes operational: from 19,000 to over 43,000 m²LU-VE 扩建后的中国天门工厂投产:从 19,000 平方米扩大到 43,000 平方米以上
  2. Jul 20252025 年 7 月 Munters breaks ground on its Daleville, Virginia expansion for data-center cooling production (chillers)Munters 在弗吉尼亚州 Daleville 动工扩建数据中心冷却产品生产(冷水机组)
  3. Jul 20252025 年 7 月 LU-VE reports that production of large GIANTS EHDV dry coolers has started at TianmenLU-VE 报告天门工厂已开始生产大型 GIANTS EHDV 干冷器
  4. May 20262026 年 5 月 LU-VE inaugurates 20,000 m² of new production area in Jacksonville, TexasLU-VE 在得克萨斯州杰克逊维尔启用 20,000 平方米新生产区
  5. Sep 20262026 年 9 月 Munters inaugurates the expanded Daleville campus (52,000 m²) and starts local chiller manufacturingMunters 启用扩建后的 Daleville 园区(52,000 平方米),开始本地生产冷水机组

Who earns the revenue谁获得这部分收入

Listed companies in the registry behind the products on this page: 本页产品背后、在上市公司名单中的公司:CarrierCarrier, ModineModine, MuntersMunters, Shenling申菱环境, Trane TechnologiesTrane Technologies, VertivVertiv. Outside the registry: 不在名单中:Güntner (private非上市); Kelvion (private; SLB agreed to acquire it in 2026非上市;SLB 已于 2026 年同意收购); LU-VE (listed in Milan; not in this registry米兰上市;不在本名单中); EVAPCO (private非上市); Baltimore Aircoil (BAC) (part of Amsted Industries (private)Amsted Industries 旗下(非上市)); Alfa Laval (listed in Stockholm; not in this registry斯德哥尔摩上市;不在本名单中). See the value-chain map查看产业链地图 · Chillers deep dive冷水机组深度分析 · CDU deep diveCDU 深度分析

Method方法

Specifications come from each vendor’s datasheet, brochure or product page; each source was extracted by two different models and ruled against the saved text. Events come from vendor and buyer announcements; each was checked by script on the page and by an independent model. Evidence cut-off 2026-10-13. Personal research, not investment advice.规格来自各厂商的数据表、样本或产品页;每个来源由两个不同模型分别提取,并对照保存的原文裁定。事件来自厂商和收购方的公告,每条都经脚本在原页面核对并由独立模型复核。证据截止 2026-10-13。个人研究,不构成投资建议。

Database view: the full matrix, dry and adiabatic数据库视图:完整矩阵,干式与绝热19 rows19 行
Showing显示 19

Vendors state 70 of 171 displayed cells (a capacity range counts as stated). A value appears only where its conditions are stated; ranges are not ranked, and rows are sorted by company. °F is converted to °C and MBH to kW (1 MBH = 0.293 kW). ○ = not stated by the vendor (explained once here, not repeated in words in each cell).表中 171 个单元格里,厂商披露了 70 个(容量范围算作已披露)。数值只在写明工况时才放在工况列;范围不做排名,行按公司排序。°F 换算为 °C,MBH 换算为 kW(1 MBH = 0.293 kW)。○ = 厂商未标称(只在此说明一次,不在每格重复文字)。

Dry (12 lines)干式(12 个系列)

Company and line公司与产品Capacity kW容量 kWFluid in / out °C进 / 出液 °CAmbient at rating °C额定环境温度 °CRating fluid额定工况介质Fans (vendor wording)风机(厂商原文)Sound噪声Footprint L × W mm占地 长 × 宽 mmWater use (vendor wording)用水(厂商原文)Coil layout盘管布置Notes说明
Alfa Laval
Cooling Pod
family 500–1,000系列 500–1,000
“500 and 1000 kW*”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露2 or 3 fans, 60 in2 或 3 台风机,60 英寸not stated未披露6,066 × 2,438none (waterless)无(不用水)straight finned tube bundles直翅片管束'500 and 1000 kW* modular designs'; '*Actual heat transfer varies based on ambient conditions.'“500 和 1000 kW 模块化设计”;“实际换热量随环境条件变化”。
Baltimore Aircoil (BAC)
TrilliumSeries TDFS
up to (nominal family maximum) 最高(系列名义最大值) 2,931
“up to 10,000 MBH”
46.1 / 40.635not stated未披露4 fans, belt drive with VFD4 台风机,皮带传动,变频not stated未披露11,608 × 3,531none (dry only)无(纯干式)vertical coil立式盘管'Nominal capacity based on a 115° F EWT and 105° F LWT at a 95° F dry bulb'. The brochure does not say which model reaches 10,000 MBH.“名义容量基于 115°F 进水、105°F 出水、95°F 干球温度”。样本没有说明哪个型号达到 10,000 MBH。
Carrier
09VE
family 100–1,870系列 100–1,870
“100 to 1870 kW”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露6–20 fans, 800 / 910 mm, AC or EC6–20 台风机,800 / 910 mm,AC 或 ECnot stated未披露3,550–11,660 × 2,305–2,420 by model, without options按型号 3,550–11,660 × 2,305–2,420,不含选配optional spray misting可选喷雾not stated未披露Family range only; optional water misting into the air flow.只有系列容量范围;可选向进风喷雾。
EVAPCO
eco-Air EAW-HD APEX
family 2,655–3,367系列 2,655–3,367
“9,060 MBH to 11,490 MBH”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露belt-drive NEMA motors, VFD ready皮带传动 NEMA 电机,支持变频not stated未披露not stated未披露not stated未披露double stack双层叠放CTI-certified nominal range (CTI ATC-105DS) without conditions on the page.CTI 认证的名义容量范围(CTI ATC-105DS),页面未写工况。
Güntner
V-shape VARIO (GFD / GFW)
family 47–2,040系列 47–2,040
“GFD 75 - 2,040; GFW 47 - 740”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露up to 2 × 12 fans最多 2 × 12 台风机not stated未披露not stated未披露optional hydroBLU pads可选 hydroBLU 湿帘V-shapeV 型Range per type: GFD 75–2,040 kW, GFW 47–740 kW; hydroBLU pads optional.按类型给出范围:GFD 75–2,040 kW,GFW 47–740 kW;可选 hydroBLU 湿帘。
Kelvion
Mega-Bay / Giga-Bay
family 1,500–8,000系列 1,500–8,000
“1.5–4 MW (Mega-Bay), 4–8 MW (Giga-Bay) per module”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露Mega-Bay: 3 fans up to 14 ft; Giga-Bay: up to 22 ftMega-Bay:3 台最大 14 英尺;Giga-Bay:最大 22 英尺not stated未披露not stated未披露not stated未披露not stated未披露Per-module ranges without conditions: Mega-Bay 1.5–4 MW (three fans up to 14 ft), Giga-Bay 4–8 MW (fans up to 22 ft).每个模块的容量范围,未写工况:Mega-Bay 1.5–4 MW(三台最大 14 英尺风机),Giga-Bay 4–8 MW(最大 22 英尺风机)。
Kelvion
V-shape dry cooler (LV)
family 6–2,140系列 6–2,140
“6 kW - 2140 kW”
range printed with conditions范围附有工况
40 / 3525water水1–22 fans, 800–960 mm, AC or EC1–22 台风机,800–960 mm,AC 或 ECnot stated未披露largest type up to 13,200 × 2,503最大型号至 13,200 × 2,503optional adiabatic system可选绝热系统V-shapeV 型Capacity range 6–2,140 kW printed with its conditions directly beneath it: water, tA1 = 25 °C air, tL1 = 40 °C in, tL2 = 35 °C out. A conditioned family range, not one unit's rating.容量范围 6–2,140 kW,下方直接印有工况:水,tA1 = 25 °C 空气,tL1 = 40 °C 进液,tL2 = 35 °C 出液。这是带工况的系列范围,不是单台额定值。
LU-VE
Alfa V Mega VXX3
family 200–2,000系列 200–2,000
“200 to 2,000 kW (EN1048 standard)”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露AC or EC, 910 / 1,000 mmAC 或 EC,910 / 1,000 mmnot stated未披露not stated未披露not stated未披露V-shapeV 型Family range per EN 1048 without numerical rating temperatures.按 EN 1048 给出系列范围,未写额定温度。
Modine
ECO Vshape-W
family 100–2,000系列 100–2,000
“From 100 to 2000 kW”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露4–18 fan modules, 800 / 910 mm, AC or EC4–18 个风机模块,800 / 910 mm,AC 或 ECnot stated未披露not stated未披露not stated未披露V-shapeV 型Family range only.只有系列容量范围。
Munters
DGV V-shape dry cooler
family 140–1,680系列 140–1,680
“from 140 to 1680 kW”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露2–20 fans, 800 / 910 mm2–20 台风机,800 / 910 mmnot stated未披露not stated未披露not stated未披露V-shapeV 型Family range only.只有系列容量范围。
Trane
Dry-cooler offering (Europe)
family 250–500系列 250–500
“250 kW and 500 kW nominal duty”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露Nominal duties without rating conditions; units can be combined in multiples.名义容量,未写工况;可多台组合。
Vertiv
Liebert direct-drive drycooler
275
940
“938 MBH (275 kW)”
48.9 / —3540% ethylene glycol40% 乙二醇8 direct-drive propeller fans, ≤ 660 mm8 台直驱轴流风机,≤ 660 mm81.5 dB(A) at 1.5 m1.5 m 处 81.5 dB(A)4,356 × 2,213not stated未披露flat平置Largest standard 60 Hz model; 'Capacity shown is Drycooler THR at sea level'. Leaving fluid temperature not stated. 50 Hz: 242 kW.最大的 60 Hz 标准型号;“容量为海平面处干冷器总排热量”。未写出水温度。50 Hz 时为 242 kW。

Adiabatic or evaporative assist (7 lines)绝热或蒸发辅助(7 个系列)

Company and line公司与产品Capacity kW容量 kWFluid in / out °C进 / 出液 °CAmbient at rating °C额定环境温度 °CRating fluid额定工况介质Fans (vendor wording)风机(厂商原文)Sound噪声Footprint L × W mm占地 长 × 宽 mmWater use (vendor wording)用水(厂商原文)Coil layout盘管布置Notes说明
Baltimore Aircoil (BAC)
Trillium TRFS adiabatic cooler
not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露factory-installed wetted pads, used when needed工厂预装湿帘,按需启用not stated未披露Brochure states no capacity or rating conditions.样本未写容量和额定工况。
EVAPCO
eco-Air EAW-DA Double Stack
family 806–2,474系列 806–2,474
“2,750 MBH to 8,440 MBH”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露belt-drive NEMA motors皮带传动 NEMA 电机not stated未披露not stated未披露wetted adiabatic pads绝热湿帘double stack双层叠放Nominal range without conditions.名义范围,未写工况。
Güntner
High Density with hydroBLU
family 733–3,165系列 733–3,165
“2,500 – 10,800 MBH”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露4–22 fans, 36 in4–22 台风机,36 英寸not stated未披露3,581–13,233 × 3,581 (11′9″–43′5″ × 11′9″)3,581–13,233 × 3,581(11′9″–43′5″ × 11′9″)hydroBLU pads above a threshold超过阈值启用 hydroBLU 湿帘not stated未披露Nominal range without conditions; pads inactive below a set threshold; 'up to 70% less water than cooling towers'.名义范围,未写工况;低于设定阈值时湿帘不工作;“比冷却塔最多少用 70% 的水”。
LU-VE
Alfa V Mega VXX3 WETWALL
family 200–2,000系列 200–2,000
“200 to 2,000 kW (EN1048 standard)”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露WETWALL wetted panels; recirculation availableWETWALL 湿帘板;可选循环用水V-shapeV 型Same EN 1048 range as the dry version; no separate adiabatic capacity.与干式版本相同的 EN 1048 范围;没有单独的绝热容量。
Modine
ECO dry coolers, adiabatic configurations
not stated未披露not stated未披露not stated未披露not stated未披露primarily EC axial fans主要为 EC 轴流风机not stated未披露not stated未披露adiabatic pads or spray绝热湿帘或喷淋not stated未披露Marketing brochure; no capacities or ratings.宣传样本,没有容量和额定值。
Munters
DMI with INTELLIBATIC
family 50–1,500系列 50–1,500
“from 50 to 1500 kW”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露1–22 fans, 800 / 910 mm1–22 台风机,800 / 910 mmnot stated未披露not stated未披露INTELLIBATIC adiabatic systemINTELLIBATIC 绝热系统not stated未披露Family range only.只有系列容量范围。
Shenling
Data-center evaporative dry cooler (数据中心蒸发冷却干冷器)
family 500–2,000系列 500–2,000
“冷量覆盖500~2000kW”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露evaporative assistance蒸发冷却辅助not stated未披露Family range only; dry and evaporative capacities not separated.只有系列容量范围;未区分干式与蒸发冷却容量。